Wet Differential Pressure Transmitter Dwyer Series 645-1
Wet Differential Pressure Transmitter Dwyer Series 645-1
-
Series 645 Wet/Wet Differential Pressure Transmitters are designed for use with compatible gases and liquids which can be applied to both the pressure and reference ports.
-
Quick response capacitance sensor delivers a 4 to 20 mA output signal proportional to differential pressure with ±.25% accuracy.
-
The Series 645 transmitters are ideal for process control, filter condition monitoring, refrigeration equipment, pump speed control, HVAC equipment, and liquid level measurement.
-
For ease of installation and maintenance, order optional 3-valve manifold assembly. Bleed ports allow for total elimination of air in the line and pressure cavities.
Specifications:
-
Service:Compatible gases or liquids on both pressure and reference sides.
-
Wetted Materials:17-4 PH stainless steel, 300 Series stainless steel, fluoroelastomer and silicone O-rings and bleed screw seals.
-
Accuracy:±0.25% FS (RSS).
-
Temperature Limits:Operating: 0 to 175°F (-22 to 80°C); Storage: -65 to 260°F (-54 to 126°C).
-
Pressure Limits:(High side) 1 to 5 psi: 20 x FS, 10 to 25 psi: 10 x FS, 50 psi: 5 x FS, 100 psi: 2.5 x FS; (low side) 2.5 x FS.
-
Thermal Effects:(includes zero and span) ±0.02% FS/°F, 30 to 150°F (-1 to 65°C).
-
Power Requirements:11 to 30 VDC.
-
Output Signal:4 to 20 mA, 2-wire.
-
Zero and Span Adjustments:Adjustable, ±1 mA, non-interactive.
-
Response Time:30 to 50 ms.
-
Loop Resistance:0 to 1000Ω.
-
Electrical Connection:Barrier strip terminal block with conduit enclosure and .875" (22 mm) diameter conduit opening.
-
Process Connection:1/4"-18 female NPT.
-
Housing:Stainless steel/aluminum, NEMA 4X (IP56).
-
3-Valve Manifold Assembly
-
Process Connection:1/4"-18 female NPT.