Wet Differential Pressure Transmitter Dwyer Series 629
Wet Differential Pressure Transmitter Dwyer Series 629
-
The Series 629 Differential Pressure Transmitter monitors differential pressure of air and compatible gases and liquids with 0.5% accuracy.
-
The design employs dual pressure sensors converting pressure changes into a standard 4-20 mA output signal for two wire circuits. Small internal volume and minimum moving parts result in exceptional response and reliability.
-
Terminal block zero and span adjustments are easily accessed under the top cover. The Series 629 Differential Pressure Transmitter is designed to meet NEMA 4X (IP66) construction.
Applications:
-
Lab Fume Hood Control
-
Clean Room Applications
-
Flow Measurements & Controls
-
Filter Monitoring
-
Furnace Draft Measurement
-
Process Control
Specifications:
-
Service:Compatible gases and liquids.
-
Wetted Materials:Without valve: 316, 316L SS. Additional wetted parts with 3-way valve option: Buna-N, silicone grease, PTFE, brass 360, copper, reinforced acetal copolymer.
-
Accuracy:±0.5% F.S. (includes linearity, hysteresis, and repeatability).
-
Temperature Limits:0 to 200°F (-18 to 93°C).
-
Compensated Temperature Limits:0 to 175°F (-18 to 79°C).
-
Pressure Limits:See Ordering page.
-
Thermal Effect:0.02%/°F (0.036%/°C) includes zero and span.
-
Power Requirements:13 to 30 VDC.
-
Output Signal:4 to 20 mA. Optional 0-5 or 0-10 VDC.
-
Loop Resistance:0-1300 ohms maximum for current output. For voltage outputs, minimum load resistance: 2000 ohms.
-
Electrical Connections:Terminal block; 1/2" female NPT conduit.
-
Process Connection:1/4" female NPT.
-
Enclosure Rating:Designed to meet NEMA 4X (IP66).
-
Mounting Orientation:Mount in any position.